Maximum cable length calculator — voltage drop limit
Size the longest run a cable can cover before voltage drop breaks your limit: enter load current, system voltage, conductor area and allowed drop, and read the maximum one-way length.
Cable & circuit
Current drawn by the load
mm² of the conductor
Line voltage — pick a preset below or type one
NEC 210.19 suggests 3% for branch circuits
One-way run you need to cover
Conductor material
Copper ρ ≈ 0.0172 Ω·mm²/m · aluminium ≈ 0.0282
Circuit type
V_drop = 2 × I × R × L
- Maximum one-way length
- 3.13m
- Maximum one-way length
- 10.28ft
- Voltage drop per 100 m
- 22.99V
- Voltage drop per 100 m
- 95.78%
Your 50 m run exceeds the 3.13 m limit — step up a conductor size, raise the voltage, or lower the current.
Quick note: 12 V / 24 V runs are almost always voltage-drop-limited — a 15 A, 24 V, 3% limit over copper 4 mm² reaches only about 5.6 m, far less than ampacity tables suggest.
About voltage-drop limits
NEC 210.19 recommends keeping branch-circuit drop to 3% and total drop (feeders plus branch) to 5%. At low voltages the limit bites fast: 3% of 24 V is only about 0.7 V of slack, so the allowable run collapses even when ampacity is comfortably met. Long low-voltage runs usually need a larger gauge than ampacity alone would suggest.
Related parts
Browse related parts:
Frequently asked questions
How is maximum cable length calculated from voltage drop?
The tool computes conductor resistance per kilometre as R = ρ × 1000 ÷ A, with copper at about 0.0172 Ω·mm²/m and aluminium at 0.0282. Maximum one-way length is the allowed voltage (V × drop% ÷ 100) divided by the drop factor k × current × R, where k is 2 for single-phase or √3 for three-phase.
Why is 3% the default voltage drop limit?
NEC 210.19 recommends keeping branch-circuit drop to 3% and total drop (feeder plus branch) to 5%. Because the default system voltage is 24 V, 3% leaves only about 0.7 V of slack, which is why low-voltage runs reach their maximum length very quickly.
Why do 12 V and 24 V runs need such thick conductors?
Low-voltage circuits are almost always voltage-drop-limited before ampacity. As the tool notes, a 15 A, 24 V run at a 3% limit over copper 4 mm² reaches only about 5.6 m — far less than ampacity tables suggest. Raising the voltage or lowering the current lengthens the allowable run fastest.
How it works
IC Source Direct sizes long runs by conductor resistance rather than ampacity alone. Line resistance follows R = ρ × L ÷ A with copper at ≈ 0.0172 Ω·mm²/m and aluminium at ≈ 0.0282, and the drop is 2 × I × R × L for single-phase or √3 × I × R × L for three-phase. Working the allowed drop back against these terms gives the longest one-way run the cable can cover.
IC Source Direct provides this tool for reference only.
More calculators
- AWG to mm² converter
- Voltage drop calculator
- Conduit fill calculator
- Copper vs aluminium calculator
- Cable current calculator
- Coax attenuation calculator
- Ohm’s law & power calculator
- Cable ampacity derating calculator
- Crimp terminal & contact sizer
- IP rating calculator
- Contact resistance calculator
- Insulation resistance calculator
- Connector pitch converter
- Skin depth calculator
- Connector mating cycles calculator
- AWG to circular mil converter
- Wire size by voltage drop calculator
- Cable unit converter (AWG / SWG / mm²)
- Conductor resistance temperature calculator
- Multi-segment voltage drop calculator
- Wire harness current capacity calculator
- Coaxial impedance calculator
- Twisted pair impedance calculator
- Shield effectiveness calculator
- Wire harness weight calculator
- Crimp joint resistance calculator
- Differential pair impedance calculator
- Propagation delay calculator
- Wire harness length planner
- PoE power budget calculator
- Cable bend radius calculator